Details
Dimensions
Gas Gun Assembly
Combustion Chamber Dimensions
Minimum Combustion Chamber Dimensions (inches) | ||||
Input Firing Rate in MBH | Length ‘L’ | Width ‘W’ | Height “H” | Burner Head Centerline to floor ‘A’ |
300-400 | 18 | 12 | 12 | 6 |
400-600 | 22 | 14 | 14 | 7 |
600-900 | 26 | 16 | 16 | 8 |
900-1,200 | 30 | 18 | 18 | 9 |
Gas Train Assembly
(Typical Gas Train, other configurations are available)
Specifications
Input Firing Range*: 300 – 1200 MBH
Firing Mode: On-Off or On/Off with Low Fire Start
Fuel:
-
- Natural Gas: 0.64 Specific Gravity
- Gas (LP): 1.53 Specific Gravity
Required Input Gas Supply Pressure:
-
- 3.5″ WC minimum
- 14″ WC maximum
Input Voltage**: 120 Vac + 10% / -15%; 60 Hz Input
Input Current: 4.8 Amp
Gas Train: UL Standard 24V
Burner Control: Beckett 7590C Direct Ignition
Flame Detection: Flame Rectification
Igniter: Beckett 7474002 Gas Igniter
Motor: 1/3 HP, 3450 RPM 120 volt/ 60 hz, single phase
Combustion Air Proving: Differential Pressure Switch
Weight: 40 lbs.
Mounting Orientation: Up to 90° from upright with motor shaft horizontal
Dimensions: 11.8″ x 13.5” x 20.6”
Acceptable Ambient Temperature Range: -4˚F to +104˚F
Acceptable Ambient Humidity: 5% – 95% RH non-condensing
* For altitudes higher than 2,000 feet, derate the burner capacity 4% for each 1,000 feet above sea level.
** This burner is not approved for use in 50 Hz applications.
Beckett CG10-24 Gas Burner Cross-Reference
Beckett Burner | Beckett Firing Rates | PowerFlame JR Burner | PowerFlame C Burner | Riello | Gordon Piatt | Webster |
CG10.1 to CG10.4 | 300 to 1000 MBH | JR15A | CR1-G-10 | G400 | N/A | N/A |
CG10.5 to CG10.6 | 1000 to 1200 MBH | JR30A | CR1-G-12 | G750 | R6.2-G | JB1G-03 |
The Beckett CG10 Gas Burner pairs with the following Commercial Products:
-
- Commercial Oil/Gas Burner Motors
- 21341U – Split Phase (1/3HP; 3450RPM; 120Vac)
- Commercial Oil Burner Pumps
- Suntec: 21188U – B2YA-8916 (2- phase; 7GPH@100psi)
- Suntect: 21369U – B2TA-8248 (2- phase; 8GPH@100psi)
- New York City Oil Pumps/DAR Kits: 51871U – B2TA-8248/DAR Mounted (single phase; 8GPH@100psi)
- Transformer & Electronic Igniters with base plate
- 51824U – Igniter with Beckett ‘S’ Base
- 51840U – Igniter with Carlin 200 Base
- Commercial Oil/Gas Burner Motors
Commercial Burner Control Panels
Our heavy duty 16-gauge steel control boxes can be mounted on any of our commercial CF & CG Series burners. They come in 2 convenient sizes (12″ x 12″, 16″ x 12″) according to your burner needs. We have a variety of light indicators, voltage configurations, and other options to chose from.
Downloads & Links
Warranty
Please note, all warranty claims must be initiated through an authorized Beckett supplier/distributor. Distribution policies will not allow Beckett to directly handle warranty claims with installers and/or consumers.