Details
Overall Dimensions

Combustion Chamber Dimensions

Firing Rate (gph) | Minimum Dimensions | |||
Refractory Lined |
Wet-based Boilers | |||
A | L | A | L | |
0 to 5 | 7.0″ | 25.0″ | 7.0″ | 25.0″ |
5 to 10 | 8.0″ | 35.0″ | 8.0″ | 40.0″ |
Specifications
Operation: On/Off
Rate: 4.00 to 10.00 GPH
Fuels:
- No. 1 or No. 2 heating oil (ASTM D396)
- ASTM D396 for B6 – B20 biodiesel blends
Motor:
- 1/2 HP 3450 rpm
- 120/60 Hz Standard
- 6.5 amps @ 120 VAC
- Optional Voltages (60 Hz or 50 Hz):
- 240 VAC/1-PH
- 208, 240, 480 VAC/3-PH
Ignition Trans.: Continuous Duty, 120V/12,000V
Housing: Cast aluminum
Fuel Unit: 100 to 300 psig
Oil Nozzle: 45˚ to 70˚ Solid
Cross-References
Burner Cross-Reference:
- Carlin: 601CRD
Commercial Burner Motors:
- 21401U – Split Phase (1/2HP; 3450RPM; 120-208/320Vac)
- 21638U – Split Phase (1/2HP; 3450RPM; 208/240-480Vac)
Commercial Burner Pumps:
- Suntec: 21259U – B2TA-8851 N642R (2- phase; 16GPH@100psi)
- New York City Oil Pumps / DAR Kits: 21528U – B2TA-8852 N642R/DAR Mounted (2- phase; 23GPH@100psi)
Transformer & Electronic Igniters with base plate:
- 51214U – 12,000 volt Universal Transformer
Typical Sequence of Operation

One-pipe Oil Flow with “B” Pump

Two-pipe Oil Flow with “B” Pump

Legend
a Return port; b Nozzle port; c Oil valve; d Nozzle & adapter; g Inlet port; k Return line to oil tank; p Air bleed valve
Beckett Commercial Burner Control Panels
The burner control panel is available on all Beckett Commercial Oil and Gas burners and can be built to your specifications and functions. It is burner mounted on the CF1000, CF1400, CF2300, CF2500 and CF3500 oil burners, and is available as a remote mounted panel for the CF500 and CF800 oil burners. The control panel is burner mounted on the CG15, CG25 and CG50 gas burners, and is available as a remote mounted panel for the CG10 gas burner.

Downloads & Links
Warnings (prop65)
Warranty
Please note, all warranty claims must be initiated through an authorized Beckett supplier/distributor. Distribution policies will not allow Beckett to directly handle warranty claims with installers and/or consumers.