Specifications for nozzles, air tube combinations, and other initial settings.
Service bulletins and product updates.
Training videos and PowerPoint presentations.
Solutions to common issues.
Look through exploded views to find the part you need.
A library of product manuals and supplemental guides.
View the limited warranty for all Beckett products.
Submit a return material authorization (RMA) Request.
Frequently asked questions, and a list of affected products.
Hands-on, practical installation, application, and operation training on Beckett’s latest products — in-person with the industry’s foremost authorities. Register today.
Informative and technical training resources from the leading experts in the heating industry — now available online, on-demand, and FREE.
Our most popular product-related instructional / training videos for the most relevant and widely seen products and applications you’ll find in the field.
For over 80 years Beckett products have been the number one choice of homeowners and contractors for their furnaces, boilers, and water heaters. As North America's foremost brand of burners, Beckett continues to provide industry leading design, reliability, and support. All backed by a comprehensive warranty program that ensures you will have years of trouble-free operation.
As North America's leading brand of burners, you can have peace of mind in using a Beckett burner on your next commercial project. With the environment in mind, we have the most comprehensive lineup of biofuel rated burners in the industry. Supported by a broad network of trained technicians, choosing a Beckett burner for your next commercial project ensures your building will have years of trouble-free operation while reducing your equipment’s impact on the environment. A return on investment for future generations.
When the sun is blazing and you're responsible for keeping Americas roads maintained, you'll want a burner that's as hard working as you are. Beckett's lineup of DC burners provides mobile heat for all types of road maintenance equipment. With their ease of service and parts availability from coast to coast, you can ensure the job gets done when the heat is on.
For over 30 years Beckett has served the pressure washer market in providing rugged yet reliable burners and components for the pressure washer industry. Our compact DC powered burners provide off-grid dependable operation in the wettest of environments. All backed by a comprehensive warranty program that ensures you will have years of trouble-free operation. So, when the "pressure" is on to get a job done, you can rely on Beckett to keep you in "hot water".
With a wide range of capacities, Beckett has served the needs of the agricultural industry for over 20 years. Our proven experience in the combustion field allows us to work with appliance engineers to ensure the strictest of parameters are met when drying organic products. Beckett's modular burner platform provides the most flexibility in applications while offering the most comprehensive lineup of biofuel rated burners in the industry. This ensures efficient reliable heat for future generations.
When freezing temperatures hit your job sites and you need dependable heat, consider Beckett for the job. From the Arctic circle to Antarctica, Beckett has proven to be the burner of choice in the harshest most remote environments. Our robust, user-friendly design provide quick maintenance and dependable operation to ensure your site stays warm.
Beckett burners and components are used in food processing applications all over the world. From bakery ovens, coffee roasters, dehydrators, and industrial process lines, Beckett robust, reliable products reduce line down time and ensure an uninterrupted output.
From tank to flame, Beckett delivers the most technically advanced product line in the industry — burners, igniters, controls, and accessories designed to meet the performance requirements of the industry while meeting the demands of biofuels to reduce emissions and meet carbon reduction goals. Explore all that Beckett has to offer below by selecting a brand, product category, or simply filtering through the entire product offering.
With the acquisition of Westwood Products in 2021, Beckett added depth and diversity to its already impressive catalog. In addition to the Tigerloop suite of Oil Dearaetors which has been transitioned to our Beckett branded offering, our Westwood by Beckett product offering includes fuel filters, electrodes, tank accessories, and many other HVAC service and repair items. The line includes B100 filters which, in conjunction with the Tigerloop Bio models, completes Beckett’s industry leading suite of B100 rated components from tank-to-flame and further positions as the market leader in the drive to alternative fuels.
For over 80 years Beckett products have been the number one choice of homeowners and contractors for their furnaces, boilers, and water heaters. As North America's foremost brand of burners, Beckett continues to provide industry leading design, reliability, and support. All backed by a comprehensive warranty program that ensures you will have years of trouble-free operation.
As North America's leading brand of burners, you can have peace of mind in using a Beckett burner on your next commercial project. With the environment in mind, we have the most comprehensive lineup of biofuel rated burners in the industry. Supported by a broad network of trained technicians, choosing a Beckett burner for your next commercial project ensures your building will have years of trouble-free operation while reducing your equipment’s impact on the environment. A return on investment for future generations.
When the sun is blazing and you're responsible for keeping Americas roads maintained, you'll want a burner that's as hard working as you are. Beckett's lineup of DC burners provides mobile heat for all types of road maintenance equipment. With their ease of service and parts availability from coast to coast, you can ensure the job gets done when the heat is on.
For over 30 years Beckett has served the pressure washer market in providing rugged yet reliable burners and components for the pressure washer industry. Our compact DC powered burners provide off-grid dependable operation in the wettest of environments. All backed by a comprehensive warranty program that ensures you will have years of trouble-free operation. So, when the "pressure" is on to get a job done, you can rely on Beckett to keep you in "hot water".
With a wide range of capacities, Beckett has served the needs of the agricultural industry for over 20 years. Our proven experience in the combustion field allows us to work with appliance engineers to ensure the strictest of parameters are met when drying organic products. Beckett's modular burner platform provides the most flexibility in applications while offering the most comprehensive lineup of biofuel rated burners in the industry. This ensures efficient reliable heat for future generations.
When freezing temperatures hit your job sites and you need dependable heat, consider Beckett for the job. From the Arctic circle to Antarctica, Beckett has proven to be the burner of choice in the harshest most remote environments. Our robust, user-friendly design provide quick maintenance and dependable operation to ensure your site stays warm.
Beckett burners and components are used in food processing applications all over the world. From bakery ovens, coffee roasters, dehydrators, and industrial process lines, Beckett robust, reliable products reduce line down time and ensure an uninterrupted output.
Specifications for nozzles, air tube combinations, and other initial settings.
Rec No | Appliance Mfg | Appliance Model | Fuel Type | Burner Model | Chassis Part No. | Head | Static Plate / Stop Screw | Vent Type | Rate GPH | Nozzle | Alt. Nozzle | Baffle | Burner ATC | Welded Insertion | Pump (PSIG) | Shutter / Band | Insertion Depth | See Note | Note | Updated Date |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Rec No | Appliance Mfg | Appliance Model | Fuel Type | Burner Model | Chassis Part No. | Head | Static Plate / Stop Screw | Vent Type | Rate GPH | Nozzle | Alt. Nozzle | Baffle | Burner ATC | Welded Insertion | 0 | Shutter / Band | Insertion Depth | 0 | Note | Updated Date |
70930 | A.O. Smith | COF-455 | #2 [UpTo B20] | SF | B711 | F22 | 2-3/4" | Chimney | 3.25 | 3.25 X 80°B | N/A | SF53FP | 58020169 | 100 | - | 1" | 26 | Burner requires Part Number 21295 four-second timer and solenoid valve. | 1/8/25 | |
70931 | A.O. Smith | COF-700 A | #2 [UpTo B20] | SF | B711 | F31 | 2-1/4" | Chimney | 5.0 | 5.00 X 80°B | N/A | SF53NN | 58020109 | 100 | 5/4 | 1" | 26 | Burner requires Part Number 21295 four-second timer and solenoid valve. | 2/4/25 | |
72429 | A.O. Smith | COF-199 | #2 [UpTo B20] | AFG | BR100 | F12 | 2-3/4" | Chimney | 1.4 | 1.35 X 80°B | N/A | AF53XO | - | 110 | 6/0 | 1-1/2" | 2/4/25 | |||
70927 | A.O. Smith | COF-245 | #2 [UpTo B20] | AFG | BR100 | F12 | 2-3/4" | Chimney | 1.75 | 1.75 X 80°B | N/A | AF53XO | - | 100 | 9/0 | 1-1/2" | 1/3/25 | |||
70926 | A.O. Smith | 400MBTU | #2 [UpTo B20] | AF | BR200 | F31 | - | Chimney | 2.75 | 2.75 X 80°B | N/A | AF65XS | - | 100 | - | - | 1/7/25 | |||
70929 | A.O. Smith | COF-385 | #2 [UpTo B20] | SF | B711 | F16 | 2-3/4" | Chimney | 2.75 | 2.75 X 80°B | N/A | SF53NU | 58020260 | 100 | 5/0 | 1" | 26 | Burner requires Part Number 21295 four-second timer and solenoid valve. | 1/8/25 | |
70928 | A.O. Smith | COF-315 | #2 [UpTo B20] | AFG | BR100 | F22 | 2-3/4" | Chimney | 2.25 | 2.25 X 80°B | N/A | AF53XP | - | 100 | 10/0 | 1-1/2" | 1/3/25 | |||
70925 | A.O. Smith | 270 MBTU | #2 [UpTo B20] | AF | BR200 | F3 | 2-3/4" | Chimney | 2.0 | 2.00 X 80°B | N/A | AF65XO | - | 100 | - | - | 2/4/25 | |||
70924 | A.O. Smith | 140MBTU | #2 [UpTo B20] | AF | BR200 | F3 | 2-3/4" | Chimney | 1.0 | 1.00 X 80°B | N/A | AF65XN | - | 100 | - | - | 2/4/25 | |||
69136 | A.O. Smith | 199MBTU | #2 [UpTo B20] | AF | BR200 | F6 | 2-3/4" | Chimney | 1.35 | 1.35 X 80°B | 0.85 X 70°AS | N/A | AF65XO | - | 100 | - | - | 1/7/25 | ||
69130 | Adams / Dornback | HEO-0.60 | #2 [UpTo B20] | NX | B8001 | 9-slot | - | Direct | 0.5 | 0.50 X 70°A | 0.85 X 70°AS | 32229 | NX50LBHS | 58020259 | 140 | 2 | 2" | 55 | Burner equipped with #32246 Heat Shield. | 2/4/25 |
69485 | Adams / Dornback | SO90 | #2 [UpTo B20] | AFG | BR100 | F3 | 2-3/4" | Chimney | 0.75 | 0.65 X 70°A | 0.50 X 70°B | N/A | AF72XNSSHS | - | 140 | - | - | 2 | “HS” on air tube combination = ceramic heat shield on combustion head., Requires stainless steel air tube. | 2/4/25 |
68962 | Adams / Dornback | SO175 | #2 [UpTo B20] | AFG | BR100 | F6 | 2-3/4" | Chimney | 1.5 | 1.25 X 70°A | 1.10 X 80°S | N/A | AF72YBSSHS | - | 140 | - | 6-1/2" | 2 | “HS” on air tube combination = ceramic heat shield on combustion head., Requires stainless steel air tube. | 2/4/25 |
69417 | Adams / Dornback | UFO90 | #2 [UpTo B20] | AFG | BR100 | F3 | 2-3/4" | Chimney | 0.7 | 0.60 X 70°A | 0.60 X 70°NS | N/A | AF72XNSSHS | - | 140 | - | - | 2 | “HS” on air tube combination = ceramic heat shield on combustion head., Requires stainless steel air tube. | 2/4/25 |
69118 | Adams / Dornback | UFO120 | #2 [UpTo B20] | AF | BR200 | F3 | 2-3/4" | Chimney | 0.85 | 0.85 X 70°A | 0.85 X 70°H | N/A | AF72XN | - | 100 | - | - | 2 | “HS” on air tube combination = ceramic heat shield on combustion head., Requires stainless steel air tube. | 1/7/25 |
69363 | Adams / Dornback | UFO105 | #2 [UpTo B20] | AFG | BR100 | F3 | 2-3/4" | Chimney | 0.9 | 0.75 X 70°A | 0.65 X 70°NS | N/A | AF72XNSSHS | - | 140 | - | - | 2 | “HS” on air tube combination = ceramic heat shield on combustion head., Requires stainless steel air tube. | 2/4/25 |
69476 | Adams / Dornback | UFO70 | #2 [UpTo B20] | AFG | BR100 | F3 | 2-3/4" | Chimney | 0.6 | 0.50 X 70°A | 0.50 X 70°NS | N/A | AF72XNSSHS | - | 140 | - | - | 2 | “HS” on air tube combination = ceramic heat shield on combustion head., Requires stainless steel air tube. | 2/4/25 |
69126 | Adams / Dornback | SO140 | #2 [UpTo B20] | AFG | BR100 | F6 | 2-3/4" | Chimney | 1.0 | 1.00 X 70°A | 0.85 X 70°B | N/A | AF72YBSSHS | - | 140 | - | 6-1/2" | 2 | “HS” on air tube combination = ceramic heat shield on combustion head., Requires stainless steel air tube. | 2/4/25 |
69528 | Adams / Dornback | HEO-0.50 | #2 [UpTo B20] | NX | B8001 | 9-slot | - | Direct | 0.5 | 0.40 X 70°A | 0.40 X 70°B*(H) | 32229 | NX50LBHS | 58020259 | 140 | 0.5 | 2" | 55 | Burner equipped with #32246 Heat Shield. | 2/4/25 |
70943 | Adams / Dornback | OCF140 | #2 [UpTo B20] | AF | BR200 | F3 | 2-3/4" | Chimney | 1.0 | 1.00 X 70°A | N/A | AF72XN | - | 100 | - | - | 2/4/25 | |||
70949 | Adams / Dornback | SO140 | #2 [UpTo B20] | AF | BR200 | F3 | 2-3/4" | Chimney | 1.0 | 1.00 X 70°A | N/A | AF72XN | - | 100 | - | - | 2 | “HS” on air tube combination = ceramic heat shield on combustion head., Requires stainless steel air tube. | 2/4/25 | |
70934 | Adams / Dornback | ACO140X | #2 [UpTo B20] | AF | BR200 | F3 | 2-3/4" | Chimney | 1.0 | 1.00 X 70°A | N/A | AF72XN | - | 100 | - | - | 2/4/25 | |||
70955 | Adams / Dornback | UFO140 | #2 [UpTo B20] | AF | BR200 | F3 | 2-3/4" | Chimney | 1.0 | 1.00 X 70°A | N/A | AF72XN | - | 100 | - | - | 2 | “HS” on air tube combination = ceramic heat shield on combustion head., Requires stainless steel air tube. | 2/4/25 | |
69957 | Adams / Dornback | UFO140 | #2 [UpTo B20] | AFG | BR100 | F3 | 2-3/4" | Chimney | 1.0 | 1.00 X 70°A | N/A | AF72XNSSHS | - | 100 | - | - | 2 | “HS” on air tube combination = ceramic heat shield on combustion head., Requires stainless steel air tube. | 2/4/25 | |
Rec No | Appliance Mfg | Appliance Model | Fuel Type | Burner Model | Chassis Part No. | Head | Static Plate / Stop Screw | Vent Type | Rate GPH | Nozzle | Alt. Nozzle | Baffle | Burner ATC | Welded Insertion | Pump (PSIG) | Shutter / Band | Insertion Depth | See Note | Note | Updated Date |
Rec No | Appliance Mfg | Appliance Boiler | Burner Model | Chassis Part No. | Air Tube Combo | High Fire Rate | Nozzle | Head Setting | Low Fire Air or Shutter | High Fire Air or Band | Low Fire Pump Press. | High Fire Pump Press. | Pressure Firing Flange | nsertion Depth | Note |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Rec No | Appliance Mfg | Appliance Boiler | Burner Model | Chassis Part No. | Air Tube Combo | High Fire Rate | Nozzle | Head Setting | Low Fire Air or Shutter | High Fire Air or Band | Low Fire Pump Press. | High Fire Pump Press. | Pressure Firing Flange | Insertion Depth | Note |
4752 | Bryan Steam Corp. | DR-250 | CF375 | BCF3907 | CF56KZ | 1.79 | 1.50 X 70°W | 1 | 10 | 0.5 | N/A | 140 | 51311 | 5.00" | - |
4797 | Bryan Steam Corp. | DR-350 | CF375 | BCF3907 | C100KZ | 2.5 | 2.00 X 80°AH | 3 | 10 | 2 | N/A | 190 | 51311 | 5.00" | - |
4809 | Bryan Steam Corp. | DR-450 | CF500 | BCF809 | CF100KK | 3.21 | 2.50 X 70°AS | 4 | 4 | 0 | N/A | 150 | 51311 | 5.00" | - |
4890 | Bryan Steam Corp. | DR-650 | CF800 | BCF403 | CF100KH | 4.64 | 4.00 X 80°SS*(H) | 3 | 7 | 0 | N/A | 140 | 51311 | 5.50" | - |
4940 | Bryan Steam Corp. | DR-850 | CF800 | BCF403 | CF100KJ | 6.07 | 5.00 X 60°SS*(H) | 2 | 8 | 8 | N/A | 150 | 51311 | 5.50" | - |
4719 | Buderus | G215-3 | AFG | BR100 | AFG50ML | 1.1 | 0.90 X 45°B | 0 | 8 | 1 | N/A | 170 | 51311 | 3.50" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
4746 | Buderus | G215-4 | AFG | BR100 | AFG50ML | 1.4 | 1.10 X 60°SS | 2 | 8 | 2 | N/A | 175 | 51311 | 3.50" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
4748 | Buderus | G215-5 | CF375 | BCF3907 | CF56KY | 1.75 | 1.35 X 60°SS*(H) | 2 | 5 | 1 | N/A | 170 | 51311 | 3.50" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
4754 | Buderus | G215-6 | CF375 | BCF3907 | CF56KZ | 2.1 | 1.75 X 60°W | 1 | 7 | 2 | N/A | 140 | 51311 | 3.50" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
4791 | Buderus | G215-7 | CF375 | BCF3907 | CF56KZ | 2.5 | 2.00 X 70°AH | 1 | 9 | 3 | N/A | 150 | 51311 | 3.50" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
4810 | Buderus | G315-5 | CF500 | BCF809 | CF80KK | 3 | 2.50 X 70°AS | 3 | 7 | 0 | N/A | 140 | 51311 | 4.75" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
4839 | Buderus | G315-6 | CF800 | BCF403 | CF80KH | 3.85 | 3.25 X 90°A | 1 | 7 | 0 | N/A | 140 | 51311 | 4.75" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
4874 | Buderus | G315-7 | CF800 | BCF403 | CF80KH | 4.7 | 4.00 X 70°SS*(H) | 2 | 10 | 0 | N/A | 140 | 51311 | 4.50" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
4840 | Buderus | G315-8 | CF1400 | BCF205 | CF66KD | 5.5 | 3.25 X 90°A | 1 | 20 | 35 | 150 | 275 | 51312 | 4.50" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
4866 | Buderus | G315-9 | CF1400 | BCF205 | CF66KD | 6.4 | 4.00 X 45°H | 3 | 25 | 40 | 150 | 275 | 51312 | 4.50" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
5030 | Buderus | G515-10 | CF2300A | BCF304 | CF102KG | 11.6 | 6.50 X 60°B | 2 | 25 | 40 | 150 | 300 | 51312 | 6.00" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
5082 | Buderus | G515-11 | CF2300A | BCF304 | CF102KG | 13 | 7.50 X 45°P*(H) | 6 | 25 | 40 | 150 | 300 | 51312 | 6.00" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
5119 | Buderus | G515-12 | CF2300A | BCF304 | CF102KG | 14.6 | 8.50 X 45°B | 8 | 30 | 70 | 150 | 300 | 51312 | 6.00" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
4891 | Buderus | G515-7 | CF1400 | BCF205 | CF102KD | 6.9 | 4.00 X 90°B | 5 | 20 | 30 | 150 | 300 | 51312 | 6.00" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
4962 | Buderus | G515-8 | CF1400 | BCF205 | CF102KD | 8.4 | 5.00 X 80°H | 9 | 30 | 43 | 150 | 275 | 51312 | 6.00" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
4975 | Buderus | G515-9 | CF2300A | BCF304 | CF102KG | 10 | 5.50 X 60°PLP | 0 | 20 | 33 | 150 | 300 | 51312 | 6.00" | Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
4954 | Buderus | G615-10 | CF2500 | BCF1809 | CF102KP | 18.5 | 5.00 X 70°H | 2 | 23 | 25 | 300 | 300 | 51630 | 6.25" | Flange requires an additional adapter plate. Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
5014 | Buderus | G615-11 | CF2500 | BCF1809 | CF102KP | 21 | 6.00 X 60°H | 5 | 27 | 40 | 300 | 300 | 51630 | 6.25" | Flange requires an additional adapter plate. Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
5038 | Buderus | G615-12 | CF3500 | BCF1308 | CF114KM | 23.5 | 6.50 X 60°B | 4 | 20 | 35 | 300 | 300 | 51630 | 6.25" | Flange requires an additional adapter plate. Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only. |
Rec No | Appliance Mfg | Appliance Boiler | Burner Model | Chassis Part No. | Air Tube Combo | High Fire Rate | Nozzle | Head Setting | Low Fire Air or Shutter | High Fire Air or Band | Low Fire Pump Press. | High Fire Pump Press. | Pressure Firing Flange | nsertion Depth | Note |
Rec No | Appliance Mfg | Appliance Model | Chassis Part No. | Input BTU | Req. Input BTU | Air Tube Combo | Head | Insertion Depth | NG Orifice Size | LP Orifice Size | Baffle | Shutter / Band | Air Band PN Slot Number | Note | Updated Date |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Rec No | Application Mfg | Appliance Model | Chassis Part No. | Input BTU | Req. Input BTU | Air Tube Combo | Head | Insertion Depth | NG Orifice Size | LP Orifice Size | Baffle | Shutter / Band | Air Band PN Slot Number | Note | Updated Date |
488 | Buderus | G115-3 | CG4001 | 96000 | 90000 | CG4BUF3 | F3G | 5.25" | 0.234 | 0.177 | 5880 | S-7 / B-0 | Blank | Blank Air Band included with Air Tube Combination. Chimney vent applications only. | 10/15/24 |
489 | Buderus | G115-4 | CG4001 | 126000 | 130000 | CG4BUF3 | F3G | 5.25" | 0.364 | 0.234 | N/A | S-5 / B-0 | 4 - Slot | Blank Air Band included with Air Tube Combination. Chimney vent applications only. | 10/15/24 |
490 | Buderus | G115-5 | CG4001 | 154000 | 145000 | CG4BUF4 | F4G | 5.25" | 0.316 | 0.234 | 5880 | S-10 / B-1 | 4 - Slot | Chimney vent applications only. | 10/15/24 |
491 | Buderus | G215-3 | CG4001 | 154000 | 145000 | CG4BUF4 | F4G | 5.25" | 0.316 | 0.234 | N/A | S-5 / B-0 | 4 - Slot | Heat Exchanger Baffles Must Be Removed to Achieve Appropriate Flue Temperature Above 325°F. | 10/15/24 |
492 | Buderus | G215-4 | CG4001 | 196000 | 190000 | CG4BUF6 | F6G | 5.25" | 0.354 | 0.256 | N/A | S-8 / B-0 | 4 - Slot | Heat Exchanger Baffles Must Be Removed to Achieve Appropriate Flue Temperature Above 325°F. | 10/15/24 |
465 | Burnham / US Boiler | MPO115 | CG4001 | 115000 | 110000 | CG4BMPOF3 | F3G | 2.00" | 0.277 | 0.266 | 5880 | S-8 / B-0 | 4 - Slot | Blank Air Band included with Air Tube Combination. | 10/15/24 |
466 | Burnham / US Boiler | MPO147 | CG4001 | 147000 | 145000 | CG4BMPOF4 | F4G | 2.00" | 0.316 | 0.234 | 5880 | S-6 / B-0 | 4 - Slot | Heat Exchanger Baffles Must Be Removed to Achieve Appropriate Flue Temperature Above 325°F. | 10/15/24 |
467 | Burnham / US Boiler | MPO189 | CG4001 | 189000 | 190000 | CG4BMPOF4 | F4G | 2.00" | N/A | 0.281 | N/A | S-10 / B-1 | 4 - Slot | Heat Exchanger Baffles Must Be Removed to Achieve Appropriate Flue Temperature Above 325°F. | 10/15/24 |
460 | Burnham / US Boiler | V83 | CG4001 | 147000 | 145000 | CG4MUF4 | F4G | 1.75" | 0.316 | 0.234 | 5880 | S-10 / B-0 | 4 - Slot | None | 10/15/24 |
459 | Burnham / US Boiler | V83 | CG4001 | 105000 | 110000 | CG4MUF3 | F3G | 1.75" | 0.277 | 0.206 | 5880 | S-7 / B-0 | Blank | Blank Air Band included with Air Tube Combination. | 10/15/24 |
461 | Burnham / US Boiler | V84 | CG4001 | 147000 | 160000 | CG4MUF4 | F4G | 1.75" | 0.348 | 0.246 | 5880 | S-10 / B-0 | 4 - Slot | None | 10/15/24 |
462 | Burnham / US Boiler | V84 | CG4001 | 189000 | 175000 | CG4MUF4 | F4G | 1.75" | 0.406 | 0.261 | N/A | S-6 / B-0 | 4 - Slot | None | 10/15/24 |
463 | Burnham / US Boiler | V85 | CG4001 | 189000 | 190000 | CG4MUF6 | F6G | 1.75" | 0.354 | 0.256 | N/A | S-8 / B-0 | 4 - Slot | None | 10/15/24 |
464 | Burnham / US Boiler | V85 | CG4001 | 231000 | 220000 | CG4MUF6 | F6G | 1.75" | 0.422 | 0.281 | N/A | S-9 / B-0 | 4 - Slot | None | 10/15/24 |
476 | Crown Boiler Co. | FWZ080 | CG4001 | 112000 | 110000 | CG4BMPOF3 | F3G | 2.00" | 0.277 | 0.266 | 5880 | S-8 / B-0 | 4 - Slot | Blank Air Band included with Air Tube Combination. | 10/15/24 |
477 | Crown Boiler Co. | FWZ100 | CG4001 | 140000 | 145000 | CG4BMPOF4 | F4G | 2.00" | 0.316 | 0.234 | 5880 | S-6 / B-0 | 4 - Slot | Heat Exchanger Baffles Must Be Removed to Achieve Appropriate Flue Temperature Above 325°F. | 10/15/24 |
478 | Crown Boiler Co. | FWZ130 | CG4001 | 182000 | 190000 | CG4BMPOF4 | F4G | 2.00" | N/A | 0.281 | N/A | S-10 / B-1 | 4 - Slot | Heat Exchanger Baffles Must Be Removed to Achieve Appropriate Flue Temperature Above 325°F. | 10/15/24 |
472 | Crown Boiler Co. | KSZ075 | CG4001 | 105000 | 110000 | CG4SFF3 | F3G | 1.75" | 0.277 | 0.206 | 5880 | S-7 / B-0 | Blank | Blank Air Band included with Air Tube Combination. | 10/15/24 |
473 | Crown Boiler Co. | KSZ100 | CG4001 | 140000 | 140000 | CG4SFF3 | F3G | 1.75" | N/A | 0.242 | N/A | S-7-1/2 / B-0 | 4 - Slot | Blank Air Band included with Air Tube Combination. | 10/15/24 |
474 | Crown Boiler Co. | KSZ125 | CG4001 | 175000 | 160000 | CG4SFF4 | F4G | 1.75" | 0.348 | 0.246 | N/A | S-6-1/2 / B-0 | 4 - Slot | None | 10/15/24 |
475 | Crown Boiler Co. | KSZ175 | CG4001 | 245000 | 220000 | CG4SFF6 | F6G | 1.75" | 0.422 | 0.281 | N/A | S-9 / B-0 | 4 - Slot | None | 10/15/24 |
468 | Crown Boiler Co. | TWZ075 | CG4001 | 105000 | 110000 | CG4SFF3 | F3G | 1.75" | 0.277 | 0.206 | 5880 | S-7 / B-0 | Blank | Blank Air Band included with Air Tube Combination. | 10/15/24 |
469 | Crown Boiler Co. | TWZ100 | CG4001 | 140000 | 140000 | CG4SFF3 | F3G | 1.75" | N/A | 0.242 | N/A | S-7-1/2 / B-0 | 4 - Slot | Blank Air Band included with Air Tube Combination. | 10/15/24 |
470 | Crown Boiler Co. | TWZ125 | CG4001 | 175000 | 160000 | CG4SFF4 | F4G | 1.75" | 0.348 | 0.246 | N/A | S-6-1/2 / B-0 | 4 - Slot | None | 10/15/24 |
Rec No | Appliance Mfg | Appliance Model | Chassis Part No. | Input BTU | Req. Input BTU | Air Tube Combo | Head | Insertion Depth | NG Orifice Size | LP Orifice Size | Baffle | Shutter / Band | Air Band PN Slot Number | Note | Updated Date |
Rec No | Appliance Mfg | Boiler Model | Burner Model | Manifold Pressure | Head Type / Setting | Firing Mode | Damper (Blue / Red) | Rate (MBH) | Insertion Depth |
---|---|---|---|---|---|---|---|---|---|
Rec No | Appliance Mfg | Boiler Model | Burner Model | Manifold Pressure | Head Type / Setting | Firing Mode | Damper (Blue / Red) | Rate (MBH) | Insertion Depth |
479 | Armstrong / Air Ease / Concord | LG-14 280 LP | CG10 | 1.9 | 10.1S / 10.1 | On/Off | - | 282 | 2.25" |
480 | Armstrong / Air Ease / Concord | LG-14 280 Nat | CG10 | 2.2 | 10.1S / 10.1 | On/Off | - | 284 | 2.25" |
481 | Armstrong / Air Ease / Concord | LG-14 350 LP | CG10 | 2.9 | 10.1S / 10.1 | On/Off | - | 350 | 2.25" |
482 | Armstrong / Air Ease / Concord | LG-14 350 Nat | CG10 | 3.4 | 10.1S / 10.1 | On/Off | - | 351 | 2.25" |
483 | Armstrong / Air Ease / Concord | LG-14 420 LP | CG10 | 1.3 | 10.3S / 10.3 | On/Off | - | 422 | 2.25" |
484 | Armstrong / Air Ease / Concord | LG-14 420 Nat | CG10 | 1.2 | 10.3S / 10.3 | On/Off | - | 419 | 2.25" |
485 | Armstrong / Air Ease / Concord | LG-14 500 LP | CG10 | 1.8 | 10.3S / 10.3 | On/Off | - | 498 | 2.25" |
486 | Armstrong / Air Ease / Concord | LG-14 500 Nat | CG10 | 1.7 | 10.3S / 10.3 | On/Off | - | 499 | 2.25" |
487 | Buderus | G315-5 | CG10 | 1.0 / 1.8 | 10.2S / 10.2 | Low Fire Start | - | 437 | 4.50" |
488 | Buderus | G315-6 | CG10 | 1.0 / 2.1 | 10.3S / 10.3 | Low Fire Start | - | 551 | 4.50" |
489 | Buderus | G315-7 | CG10 | 1.0 / 3.6 | 10.4S / 10.4 | Low Fire Start | - | 678 | 4.50" |
490 | Buderus | G315-8 | CG10 | 1.0 / 3.9 | 10.5S / 10.5 | Low Fire Start | - | 800 | 4.50" |
491 | Buderus | G315-9 | CG10 | 1.0 / 3.8 | 10.6S / 10.5 | Low Fire Start | - | 906 | 4.50" |
492 | Buderus | SB615-145 | CG10 | 0.9 / 1.8 | 10.3S / 10.3 | Low Fire Start | - | 497 | 6.50" |
493 | Buderus | SB615-185 | CG10 | 0.9 / 1.7 | 10.4S / 10.4 | Low Fire Start | - | 644 | 7.00" |
495 | Buderus | SB615-240 | CG15 | 1.2 / 3.9 | 15.1S / 15.1 | Mod | 22 / 46 | 468 | 7.00" |
494 | Buderus | SB615-240 | CG10 | 1.0 / 2.0 | 10.5S / 10.5 | Low Fire Start | - | 835 | 7.00" |
496 | Buderus | SB615-310 | CG10 | 1.2 / 2.4 | 10.6S / 10.6 | Low Fire Start | - | 1080 | 7.00" |
497 | Buderus | SB615-310 | CG15 | 1.2 / 3.4 | 15.3S / 15.3 | Mod | 28 / 60 | 641 | 7.00" |
498 | Buderus | SB615-400 | CG25 | 0.95 / 4.1 | 25.1S / 25.1 | Mod | 15 / 45 | 669 | 7.00" |
499 | Buderus | SB615-510 | CG25 | 1.0 / 4.1 | 25.3S / 25.3 | Mod | 27 / 58 | 896 | 7.00" |
501 | Buderus | SB615-640 | CG50 | 0.6 / 4.1 | 50.1S / 50.1 | Mod | 18 / 35 | 892 | 7.00" |
500 | Buderus | SB615-640 | CG50 | 0.95 / 4.1 | 50.1S / 50.1 | Low/High | 21 / 35 | 1101 | 7.00" |
502 | Buderus | SB735-1200 | CG50 | 0.7 / 5.0 | 50.5S / 50.5 | Mod | 26 / 86 | 1719 | 9.00" |
Rec No | Appliance Mfg | Boiler Model | Burner Model | Manifold Pressure | Head Type / Setting | Firing Mode | Damper (Blue / Red) | Rate (MBH) | Insertion Depth |
Informative and technical training resources from the leading experts in the heating industry
Have questions about our products? Looking for a solution to address a particular application? Looking to improve the overall productivity and profitability of your operation? Please don’t hesitate to reach out or schedule a no obligation, 1-on-1 consultation with a Beckett Technical Specialist — we’d love to help.