afii

AFII Oil Burner

Product Description

Capacities

AFII 85
  • 0.40 to 0.85 gph
  • 56,000 to 119,000 BTU/hr input
AFII 150
  • 0.75 to 1.35 gph
  • 105,000 to 189,000 BTU/hr input

Dimensions (standard)

  • Height: 13¼”
  • Width: 14½”
  • Depth: 6⅝”

Electrical Characteristics

  • Motor: 3450 rpm, NEMA M-flange, manual reset overload protection
  • Power Supply: 120 V./60Hz./1 phase
  • Ignition: 10,000 V./23 ma. secondary, continuous duty shielded transformer
  • Operating Load: 5.8 amps (maximum)
  • Alternated Voltages or Frequency: Consult Customer Service

Fuel Unit

  • Single stage or two stage

 Fuels

  • No. 1 or No. 2 heating oil (ASTM D396) only


Chassis Plan

  • Reduces Investment Up To 65%
  • Reduces Storage Space Up To 85%
  • Speeds Service Calls

Performance Capabilities

  • One-Piece Flame Retention Head – Special stainless steel construction for high performance. Time proven design. Has standard ceramic head insulator which prevents flame radiation upon the combustion components. Also fills entry openings in most combustion chambers which blocks infiltration of hot combustion gases.
  • ¼” Quick Connect Electrode Terminals – Fittings standard to our industry assure positive contact at all times. Easy to service.
  • Integrated Pump/Motor Assembly – Standard pumps. Motor has service friendly keyhole flange.
  • Sturdy Die-Cast Aluminum Housing – Has a smooth finish that keeps its like-new look for years.
  • Easily Read Air Control Dial – Locks in place for easy-to-set, precise air intake through a large single port. Regulates air on the discharge side of the blower.
  • Single, Big Air Inlet – Is on the opposite side of the burner, away from the pump, to fight lint buildup. Designed to accept 4″ air supply duct with inlet cover removed.

Burner Chassis

  • Model AF Burner Chassis
  • Type of Fuel Unit
  • Primary Control

Air Tube Combination

  • Air Tube Length (dimension A) and Firing Rate or Air Tube Combination Code (see table).

Accessories

  • Specify type of supports required.
  • Add any other items such as spare parts, related controls, valves, control panels, etc.

Air Tube Combination Chart

USABLE AIR TUBE LENGTH DIMENSION A AFII 85 FIRING RATE IN GPH AFII 150 FIRING RATE IN GPH
.40-.65 .55-.85 .75-1.00 .85-1.20 1.10-1.25 1.15-1.35
5″ FBX50HFXS FBX50HGXS FBX50HFXS FBX50HGXS FBX50HHXS FBX50HIXS
7″ FBX70HFXS FBX70HGXS FBX70HFXS FBX70HGXS FBX70HHXS FBX70HIXS
9″ FBX90HFXS FBX90HGXS FBX90HFXS FBX90HGXS FBX90HHXS FBX90HIXS

To Determine Air Tube Length

100
The Air Tube Length (Dimension A) is the distance from the front of the burner housing to the end of the tube.

Adjustable Mounting Flange Kit

102

No. 51480 Adjustable Mounting Flange Kit – A one-piece flange. Includes a flange mounting gasket.

Optional Supports

101

No. 51481 Pedestal Support – For conversion applications.

Flame Retention Heads

AFII Heads

Literature

AFII Burner Manual

Warranty Information